The treatment and conditioning of boiler feed water must satisfy three main objectives:
Continuous heat exchange
Corrosion protection
Production of high quality steam
External treatment is the reduction or removal of impurities from water outside the boiler. In general, external treatment is used when the amount of one or more of the feed water impurities is too high to be tolerated by the boiler system in question. There are many types of external treatment (softening, evaporation, deaeration, membrane contractors etc.) which can be used to tailor make feed-water for a particular system. Internal treatment is the conditioning of impurities within the boiler system. The reactions occur either in the feed lines or in the boiler proper. Internal treatment may be used alone or in conjunction with external treatment. Its purpose is to properly react with feed water hardness, condition sludge, scavenge oxygen and prevent boiler water foaming.
External treatment
The water treatment facilities purify and deaerate make-up water or feed water. Water is sometimes pretreated by evaporation to produce relatively pure vapor, which is then condensed and used for boiler feed purposes. Evaporators are of several different types, the simplest being a tank of water through which steam coils are passed to heat the water to the boiling point. Sometimes to increase the efficiency the vapor from the first tank is passed through coils in a second tank of water to produce additional heating and evaporation. Evaporators are suitable where steam as a source of heat is readily available. They have particular advantages over demineralization, for example, when the dissolved solids in the raw water are very high.
Certain natural and synthetic materials have the ability to remove mineral ions from water in exchange for others. For example, in passing water through a simple cation exchange softener all of calcium and magnesium ions are removed and replaced with sodium ions. Since simple cation exchange does not reduce the total solids of the water supply, it is sometimes used in conjunction with precipitation type softening. One of the most common and efficient combination treatments is the hot lime-zeolite process. This involves pretreatment of the water with lime to reduce hardness, alkalinity and in some cases silica, and subsequent treatment with a cation exchange softener. This system of treatment accomplishes several functions: softening, alkalinity and silica reduction, some oxygen reduction, and removal of suspended matter and turbidity.
Chemical treatment of water inside the boiler is usually essential and complements external treatment by taking care of any impurities entering the boiler with the feed water (hardness, oxygen, silica, etc.). In many cases external treatment of the water supply is not necessary and the water can be treated only by internal methods.
Internal treatment